pressure transmitter shop
Differential pressure Deltabar PMD75
shop
pressure transmitter shop
Differential pressure Deltabar PMD75
shop






Differential pressure Deltabar PMD75 – Differential pressure transmitter with metal sensor for measurement of pressure differences
| Measuring Principle | Differential pressure |
| Characteristic | Digital transmitter with metallic measuring diaphragms; Modular transmitter; Long-term stability; High static pressure/Overload resistance; Secondary process barrier |
| Supply Voltage | 4...20 mA HART: 10,5...45V DC (Non Ex); Ex ia: 10,5...30V DC; PROFIBUS PA: 9...32 V DC (Non Ex); FOUNDATION Fieldbus: 9...32 V DC (Non Ex) |
| Reference Accuracy | Standard: 0.05%; Platinum: up to 0.035% |
| Long Term Stability | 0.03 % of URL/ year; 0.05 % of URL/ 5 years; 0.08 % of URL/ 10 years |
| Process Temperature | -40°C...85°C (-40°F...185°F) |
| Ambient Temperature | -50°C...85°C (-58°F...185°F) |
| Measuring Cell | 10 mbar...250 bar (0.15 psi...3750 psi) |
| Smallest Calibratable Span | 1 mbar (0.015 psi) |
| Vacuum Resistance | 50 mbar (0.73 psi) |
| Max. Turn Down | 100:1 |
| Max. Overpressure Limit | On one side: 420 bar (6300psi) |
| Process Connection | 1/4-18NPT; RC1/4" |
| Material Process Membrane | 316L, AlloyC, Tantal, Gold-Rhodium |
| Material Gasket | Viton, PTFE, EPDM, NBR |
| Fill Fluid | Silicone oil; Inert oil |
| Material Housing | 316L, Die-cast aluminum |
| Communication | 4...20 mA HART; PROFIBUS PA; FOUNDATION Fieldbus |
| Certificates / Approvals | ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, EAC, UK Ex |
| Safety Approvals | SIL |
| Design Approvals | NACE MR0103; EN10204-3.1 |
| Marine Approvals | GL/ ABS |
| Specialities | Diagnostic functions |
| Successor | PMD75B |
The Deltabar PMD75 differential pressure transmitter with piezoresistive sensor and welded metallic membrane is used in all industries for continuous measurement in liquids, vapors and gases. The 3-key operation enables simple and reliable commissioning and operation. The integrated HistoROM data module allows easy management of process and device parameters. Designed according to IEC 61508 for use in SIL2/3 safety applications.
For level, volume or mass measurement in liquids, differential pressure monitoring as well as flow measurement (volume or mass flow) in conjunction with primary elements in gases, vapors and liquids.
Process connections: Threads
Process temperature: -40 to +85°C (-40 to +185°F)
Measuring ranges: 0.25mbar to 40bar (0.0036 to 600psi)
Accuracy: ±0.05%, “Platinum” ±0.035% (optional)
International explosion protection certificates, overfill prevention WHG, SIL, hygienic approvals, marine approvals
Best accuracy, reproducibility and long-term stability
Highest safety due to gas tight feedthrough with capabilities up to SIL2/3, certified to IEC 61508
Easy menu-guided commissioning via local display, 4 to 20mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
HistoROM data management concept for fast and easy commissioning, maintenance and diagnostics
Cost savings with modular concept for easy replacement of sensor, display or electronics
Overload-resistant up to 420bar / 42MPa / 6300psi, function-monitored
Seamless and independent system integration (HART/PA/FF)
Request Your Custom Solution & Factory Price
*We respect your privacy. Your information is used for technical quotation purposes only and will never be shared.
We use cookies to improve your experience and analyze site traffic. Choose which cookies you allow.
Required for the website to function. Cannot be disabled.
Help us understand how visitors interact with the website.
No analytics cookies are used on this site.
Used to deliver relevant advertisements and track campaigns.
No marketing cookies are used on this site.
Remember your settings and preferences for a better experience.
No preference cookies are used on this site.